R-134a PT Chart
Pressure–temperature chart for R-134a, -40 to 150°F in 1° steps. Switch to °C, kPa or bar, or look up a single value.
Quick lookup
Enter a value to get the pressure for R-134a.
| Temp °F | Pressure psig |
|---|---|
| -40 | 14.8″ Hg |
| -39 | 14.4″ Hg |
| -38 | 13.9″ Hg |
| -37 | 13.4″ Hg |
| -36 | 13.0″ Hg |
| -35 | 12.5″ Hg |
| -34 | 12.0″ Hg |
| -33 | 11.4″ Hg |
| -32 | 10.9″ Hg |
| -31 | 10.4″ Hg |
| -30 | 9.8″ Hg |
| -29 | 9.3″ Hg |
| -28 | 8.7″ Hg |
| -27 | 8.1″ Hg |
| -26 | 7.5″ Hg |
| -25 | 6.9″ Hg |
| -24 | 6.3″ Hg |
| -23 | 5.7″ Hg |
| -22 | 5.0″ Hg |
| -21 | 4.3″ Hg |
| -20 | 3.7″ Hg |
| -19 | 3.0″ Hg |
| -18 | 2.3″ Hg |
| -17 | 1.5″ Hg |
| -16 | 0.8″ Hg |
| -15 | 0.1″ Hg |
| -14 | 0.4 |
| -13 | 0.7 |
| -12 | 1.1 |
| -11 | 1.5 |
| -10 | 1.9 |
| -9 | 2.4 |
| -8 | 2.8 |
| -7 | 3.2 |
| -6 | 3.6 |
| -5 | 4.1 |
| -4 | 4.6 |
| -3 | 5.0 |
| -2 | 5.5 |
| -1 | 6.0 |
| 0 | 6.5 |
| 1 | 7.0 |
| 2 | 7.5 |
| 3 | 8.0 |
| 4 | 8.5 |
| 5 | 9.1 |
| 6 | 9.6 |
| 7 | 10.2 |
| 8 | 10.8 |
| 9 | 11.3 |
| 10 | 11.9 |
| 11 | 12.5 |
| 12 | 13.1 |
| 13 | 13.8 |
| 14 | 14.4 |
| 15 | 15.0 |
| 16 | 15.7 |
| 17 | 16.4 |
| 18 | 17.0 |
| 19 | 17.7 |
| 20 | 18.4 |
| 21 | 19.1 |
| 22 | 19.9 |
| 23 | 20.6 |
| 24 | 21.3 |
| 25 | 22.1 |
| 26 | 22.9 |
| 27 | 23.7 |
| 28 | 24.5 |
| 29 | 25.3 |
| 30 | 26.1 |
| 31 | 26.9 |
| 32 | 27.8 |
| 33 | 28.6 |
| 34 | 29.5 |
| 35 | 30.4 |
| 36 | 31.3 |
| 37 | 32.2 |
| 38 | 33.1 |
| 39 | 34.1 |
| 40 | 35.0 |
| 41 | 36.0 |
| 42 | 37.0 |
| 43 | 38.0 |
| 44 | 39.0 |
| 45 | 40.1 |
| 46 | 41.1 |
| 47 | 42.2 |
| 48 | 43.2 |
| 49 | 44.3 |
| 50 | 45.4 |
| 51 | 46.6 |
| 52 | 47.7 |
| 53 | 48.9 |
| 54 | 50.0 |
| 55 | 51.2 |
| 56 | 52.4 |
| 57 | 53.6 |
| 58 | 54.9 |
| 59 | 56.1 |
| 60 | 57.4 |
| 61 | 58.7 |
| 62 | 60.0 |
| 63 | 61.3 |
| 64 | 62.7 |
| 65 | 64.0 |
| 66 | 65.4 |
| 67 | 66.8 |
| 68 | 68.2 |
| 69 | 69.7 |
| 70 | 71.1 |
| 71 | 72.6 |
| 72 | 74.1 |
| 73 | 75.6 |
| 74 | 77.1 |
| 75 | 78.7 |
| 76 | 80.2 |
| 77 | 81.8 |
| 78 | 83.4 |
| 79 | 85.0 |
| 80 | 86.7 |
| 81 | 88.4 |
| 82 | 90.0 |
| 83 | 91.8 |
| 84 | 93.5 |
| 85 | 95.2 |
| 86 | 97.0 |
| 87 | 98.8 |
| 88 | 100.6 |
| 89 | 102.5 |
| 90 | 104.3 |
| 91 | 106.2 |
| 92 | 108.1 |
| 93 | 110.0 |
| 94 | 112.0 |
| 95 | 113.9 |
| 96 | 115.9 |
| 97 | 118.0 |
| 98 | 120.0 |
| 99 | 122.1 |
| 100 | 124.2 |
| 101 | 126.3 |
| 102 | 128.4 |
| 103 | 130.6 |
| 104 | 132.7 |
| 105 | 135.0 |
| 106 | 137.2 |
| 107 | 139.5 |
| 108 | 141.7 |
| 109 | 144.0 |
| 110 | 146.4 |
| 111 | 148.7 |
| 112 | 151.1 |
| 113 | 153.5 |
| 114 | 156.0 |
| 115 | 158.4 |
| 116 | 160.9 |
| 117 | 163.4 |
| 118 | 166.0 |
| 119 | 168.6 |
| 120 | 171.2 |
| 121 | 173.8 |
| 122 | 176.5 |
| 123 | 179.1 |
| 124 | 181.8 |
| 125 | 184.6 |
| 126 | 187.4 |
| 127 | 190.1 |
| 128 | 193.0 |
| 129 | 195.8 |
| 130 | 198.7 |
| 131 | 201.6 |
| 132 | 204.6 |
| 133 | 207.5 |
| 134 | 210.6 |
| 135 | 213.6 |
| 136 | 216.7 |
| 137 | 219.7 |
| 138 | 222.9 |
| 139 | 226.0 |
| 140 | 229.2 |
| 141 | 232.4 |
| 142 | 235.7 |
| 143 | 239.0 |
| 144 | 242.3 |
| 145 | 245.7 |
| 146 | 249.0 |
| 147 | 252.5 |
| 148 | 255.9 |
| 149 | 259.4 |
| 150 | 262.9 |
Values in italics with ″ Hg are inches of mercury vacuum (below atmospheric pressure).
About R-134a
| Type | Single-component refrigerant |
|---|---|
| ASHRAE 34 safety class | A1 |
| GWP (IPCC AR4) | 1,430 |
| Used in | Vehicle A/C (most cars built before the mid-2010s), refrigerators, chillers, medium-temperature refrigeration |
| Also sold as | HFC-134a, Suva 134a, Genetron 134a |
Widely serviced; newer light vehicles use R-1234yf.
Related charts: R-1234yf PT chart.
How to read the R-134a PT chart
- Read the gauge pressure on the low or high side.
- Find that pressure in the chart, or enter it in the quick lookup. The matching temperature is the saturation temperature.
- Superheat = suction line temperature − evaporator saturation temperature. Subcooling = condenser saturation temperature − liquid line temperature.
Need the math done for you? Use the superheat and subcooling calculator for R-134a.
FAQ
What is the pressure of R-134a at 40°F?
35.0 psig. 40°F is a typical evaporator saturation temperature for comfort cooling.
What is the pressure of R-134a at 100°F?
124.2 psig.
Where do these R-134a values come from?
They are calculated with the open-source CoolProp 8.1.0 property library and are checked against the published Arkema and Chemours charts. See the data source section below and the methodology page.
Data source and checks
Calculated with CoolProp 8.1.0 (reference equation of state). Gauge pressure is relative to 14.696 psia (sea level).
| Published chart | Points | Max difference |
|---|---|---|
| Arkema — Forane Refrigerants Pressure Temperature Chart (05-2025) | 5 | 0.04 psi (0.1%) |
| Chemours — Freon 134a Thermodynamic Properties (SI Units) | 4 | 0.16 psi (0.1%) |
R-134a values are for pure refrigerant at saturation. How the data is produced and checked.
Reference only — follow the equipment manufacturer's charging instructions.