Superheat and Subcooling Calculator

Enter gauge pressure and line temperature for each side. The calculator finds the saturation temperature from the refrigerant's PT chart — dew point for superheat, bubble point for subcooling — and compares the result with your target.

Metering device
System
Units

Superheat

Suction line, at the outdoor unit service valve

Enter pressure and line temperature.

Subcooling

Liquid line, at the outdoor unit service valve

Enter pressure and line temperature.

Targets and diagnosis

TXV systems are charged by subcooling: use the target on the outdoor unit’s rating plate or in its installation manual.

Saturation values from the R-410A PT chart.

How to calculate superheat

Superheat = suction line temperature − evaporator saturation temperature

Example with R-410A: suction pressure 118 psig gives a saturation temperature of 39.8°F. With a suction line temperature of 52°F, superheat is 12.2°F.

How to calculate subcooling

Subcooling = condenser saturation temperature − liquid line temperature

Example with R-410A: liquid line pressure 318 psig gives a saturation temperature of 99.9°F. With a liquid line temperature of 90°F, subcooling is 9.9°F.

Blends: dew point for superheat, bubble point for subcooling

Blends such as R-407C, R-448A and R-454B boil over a range of temperatures. At 63 psig, R-407C starts to boil at 28.8°F (bubble) and finishes at 39.9°F (dew). Using the wrong column on a high-glide blend shifts superheat or subcooling by several degrees. The calculator always picks the right one.

What the readings suggest

The classic patterns below come from the U.S. Department of Energy's air conditioner diagnostics guideline and Danfoss' TXV troubleshooting guide. They apply to air conditioners and heat pumps in cooling mode, with airflow already verified.

SuperheatSubcoolingTypically meansCheck
HighLowUnderchargeLeak check, then add refrigerant to target (DOE, Danfoss)
LowHighOverchargeRecover refrigerant to target (DOE)
HighHighLiquid line restriction or underfeeding metering deviceTemperature drop across the filter-drier, kinked line, plugged TXV, lost bulb charge (DOE, Danfoss)
LowLowMetering device overfeedingTXV bulb contact, position and insulation (DOE, Danfoss)

FAQ

How do you calculate superheat?

Superheat = suction line temperature − evaporator saturation temperature. Read the suction pressure, convert it to a saturation temperature with the PT chart (use the vapor/dew column for blends), and subtract it from the suction line temperature measured near the service valve.

How do you calculate subcooling?

Subcooling = condenser saturation temperature − liquid line temperature. Convert the liquid line pressure to a saturation temperature (liquid/bubble column for blends) and subtract the liquid line temperature.

What does high superheat and low subcooling mean?

It is the classic sign of an undercharged system: the evaporator is starved and little liquid collects in the condenser. A low charge also lowers evaporator pressure.

What does high superheat and high subcooling mean?

Usually a restriction ahead of the metering device, such as a plugged filter-drier or kinked liquid line, or a TXV that is underfeeding. It is not a charge problem, so adding refrigerant will not fix it.

Should I charge by superheat or subcooling?

Systems with a piston or fixed orifice are charged by superheat against the manufacturer’s target superheat chart. Systems with a TXV or EEV are charged by subcooling against the target on the outdoor unit; superheat then shows whether the valve is working.

What is a normal superheat on a TXV system?

Use the manufacturer’s range. Without one, the DOE guideline says 4–25°F may be acceptable on a TXV system.

Sources

Reference only. Follow the equipment manufacturer's charging procedure; handling refrigerant in the US requires EPA Section 608 certification.