Methodology and sources
This page explains where each number on the site comes from, so you can check it yourself. If anything here disagrees with a source you trust, please report it.
Refrigerant PT charts
Most charts are calculated with CoolProp 8.1.0, an open-source (MIT) library that implements published reference equations of state (HEOS backend).
- Single-component refrigerants use the fluid's reference equation of state.
- R-410A, R-404A and R-407C use the pseudo-pure fluid models by Lemmon (2003), which give separate bubble and dew pressures.
- R-454B and R-448A use the manufacturers' published tables. CoolProp's general mixture model differed from them by up to about 1%, while the published tables (generated with NIST REFPROP 10) agree with each other to within 0.05 psi. Whole-degree rows between published points are interpolated using ln(p) against 1/T; on a 1°F table this reproduces 5°F-spaced data to within 0.04 psi.
- Gauge pressure is absolute pressure minus 14.696 psia (sea level). Below atmospheric pressure the charts show inches of mercury vacuum.
- For blends, the liquid column is the bubble point (saturated liquid) and the vapor column is the dew point (saturated vapor).
Source and check for each chart
| Refrigerant | Data from | Checked against | Max difference |
|---|---|---|---|
| R-410A | CoolProp, pseudo-pure EOS | Arkema, Chemours | 2.22 psi (0.5%) |
| R-22 | CoolProp, reference EOS | Arkema | 0.04 psi (0.1%) |
| R-134a | CoolProp, reference EOS | Arkema, Chemours | 0.16 psi (0.1%) |
| R-404A | CoolProp, pseudo-pure EOS | Arkema, Chemours | 0.78 psi (0.2%) |
| R-454B | Chemours table | Arkema | 0.05 psi (0.2%) |
| R-290 | CoolProp, reference EOS | Hudson Technologies | 0.06 psi (<0.1%) |
| R-32 | CoolProp, reference EOS | Arkema | 0.05 psi (<0.1%) |
| R-407C | CoolProp, pseudo-pure EOS | Arkema | 0.07 psi (<0.1%) |
| R-448A | Arkema table | Solstice Advanced Materials (formerly Honeywell) | 0.17 psi (0.1%) |
| R-1234yf | CoolProp, reference EOS | Hudson Technologies | 0.13 psi (0.1%) |
The larger differences for R-410A and R-404A come from Chemours' older metric tables, which use earlier equations of state; against Arkema's REFPROP-based chart the same refrigerants differ by less than 0.2 psi.
How the check works
105 reference values were taken from the published charts below, mostly at −20, 0, 40, 100 and 130°F (or 0, 5, 38 and 55°C for metric tables). Before every build, each chart on this site is compared with them. If any value differs by more than 1 psi or 1% of the gauge pressure, whichever is larger, the site does not build, so an incorrect chart cannot go live.
R-290 and R-1234yf are checked against a refrigerant distributor's charts, because their manufacturers' tables are not openly available. Both matched within 0.15 psi.
Published charts used
- Arkema — Forane Refrigerants Pressure Temperature Chart (05-2025) (NIST REFPROP 10; retrieved 2026-11-24)
- Chemours — Thermodynamic Properties of Opteon XL41 (R-454B), Engineering Units (NIST REFPROP 10; retrieved 2026-11-24)
- Solstice Advanced Materials (formerly Honeywell) — Solstice N40 (R-448A) P-T Chart (manufacturer data; retrieved 2026-11-24)
- Hudson Technologies — R-290 Pressure Temperature Chart (distributor chart; retrieved 2026-11-24)
- Hudson Technologies — R-1234yf Pressure Temperature Chart (distributor chart; retrieved 2026-11-24)
- Chemours — Freon 410A Thermodynamic Properties (SI Units) (Martin-Hou equation of state; retrieved 2026-11-24)
- Chemours — Freon 134a Thermodynamic Properties (SI Units) (MBWR equation of state; retrieved 2026-11-24)
- Chemours — Freon 404A Thermodynamic Properties (SI Units) (PRSV equation of state; retrieved 2026-11-24)
Other fact sources
- Safety classes and blend compositions: ANSI/ASHRAE Standard 34.
- Global warming potential: IPCC Fourth Assessment Report (AR4) values, as used by the US EPA.
- Diagnostic guidance: summarized from the U.S. Department of Energy's air conditioner diagnostics guideline and manufacturers' service literature, linked on each page.
- Car A/C operating pressures: published service charts from Mastercool and Four Seasons (Standard Motor Products). These are empirical ranges, not calculated values, and are shown separately because they were measured under different conditions.
Limits
Values describe pure refrigerant at saturation. Real systems differ because of non-condensables, oil, contamination, gauge accuracy and altitude. Use the charts as a reference alongside the equipment manufacturer's charging instructions.