R-290 PT Chart

Pressure–temperature chart for R-290, -40 to 150°F in 1° steps. Switch to °C, kPa or bar, or look up a single value.

Printable PDF

Quick lookup

Enter a value to get the pressure for R-290.

R-290 pressure–temperature chart in °F and psig
Temp °FPressure psig
-401.4
-391.8
-382.2
-372.6
-363.0
-353.4
-343.9
-334.3
-324.8
-315.2
-305.7
-296.1
-286.6
-277.1
-267.6
-258.1
-248.6
-239.1
-229.6
-2110.2
-2010.7
-1911.3
-1811.8
-1712.4
-1613.0
-1513.6
-1414.2
-1314.8
-1215.4
-1116.1
-1016.7
-917.4
-818.0
-718.7
-619.4
-520.1
-420.8
-321.5
-222.2
-122.9
023.7
124.5
225.2
326.0
426.8
527.6
628.4
729.2
830.1
930.9
1031.8
1132.7
1233.6
1334.5
1435.4
1536.3
1637.2
1738.2
1839.2
1940.1
2041.1
2142.1
2243.2
2344.2
2445.2
2546.3
2647.4
2748.5
2849.6
2950.7
3051.8
3153.0
3254.1
3355.3
3456.5
3557.7
3658.9
3760.1
3861.4
3962.7
4063.9
4165.2
4266.5
4367.9
4469.2
4570.6
4672.0
4773.4
4874.8
4976.2
5077.6
5179.1
5280.6
5382.1
5483.6
5585.1
5686.7
5788.2
5889.8
5991.4
6093.0
6194.7
6296.3
6398.0
6499.7
65101.4
66103.1
67104.9
68106.6
69108.4
70110.2
71112.0
72113.9
73115.7
74117.6
75119.5
76121.4
77123.4
78125.4
79127.3
80129.3
81131.4
82133.4
83135.5
84137.6
85139.7
86141.8
87143.9
88146.1
89148.3
90150.5
91152.8
92155.0
93157.3
94159.6
95161.9
96164.3
97166.7
98169.1
99171.5
100173.9
101176.4
102178.9
103181.4
104183.9
105186.5
106189.1
107191.7
108194.3
109197.0
110199.6
111202.4
112205.1
113207.8
114210.6
115213.4
116216.3
117219.1
118222.0
119224.9
120227.8
121230.8
122233.8
123236.8
124239.9
125242.9
126246.0
127249.1
128252.3
129255.5
130258.7
131261.9
132265.2
133268.5
134271.8
135275.1
136278.5
137281.9
138285.4
139288.8
140292.3
141295.8
142299.4
143303.0
144306.6
145310.2
146313.9
147317.6
148321.4
149325.1
150328.9

Values in italics with ″ Hg are inches of mercury vacuum (below atmospheric pressure).

About R-290

TypeSingle-component refrigerant
ASHRAE 34 safety classA3
GWP (IPCC AR4)3
Used inSelf-contained commercial refrigeration, display cases, ice machines, small heat pumps
Also sold asPropane, Care 40

Growing in self-contained equipment; highly flammable, small charge limits apply.

How to read the R-290 PT chart

  1. Read the gauge pressure on the low or high side.
  2. Find that pressure in the chart, or enter it in the quick lookup. The matching temperature is the saturation temperature.
  3. Superheat = suction line temperature − evaporator saturation temperature. Subcooling = condenser saturation temperature − liquid line temperature.

Need the math done for you? Use the superheat and subcooling calculator for R-290.

FAQ

What is the pressure of R-290 at 40°F?

63.9 psig. 40°F is a typical evaporator saturation temperature for comfort cooling.

What is the pressure of R-290 at 100°F?

173.9 psig.

Where do these R-290 values come from?

They are calculated with the open-source CoolProp 8.1.0 property library and are checked against the published Hudson Technologies chart. See the data source section below and the methodology page.

Data source and checks

Calculated with CoolProp 8.1.0 (reference equation of state). Gauge pressure is relative to 14.696 psia (sea level).

Compared with published charts, checked November 24, 2026
Published chartPointsMax difference
Hudson Technologies — R-290 Pressure Temperature Chart50.06 psi (<0.1%)

R-290 values are for pure refrigerant at saturation. How the data is produced and checked.

Reference only — follow the equipment manufacturer's charging instructions.