R-454B PT Chart

Pressure–temperature chart for R-454B with liquid (bubble) and vapor (dew) columns, -40 to 150°F in 1° steps. Switch to °C, kPa or bar, or look up a single value.

Printable PDF

Quick lookup

Enter a value to get the pressure for R-454B.

R-454B pressure–temperature chart in °F and psig
Temp °FLiquid bubble, psigVapor dew, psig
-409.58.4
-3910.19.0
-3810.89.6
-3711.410.2
-3612.110.8
-3512.711.4
-3413.412.1
-3314.112.8
-3214.813.4
-3115.514.1
-3016.214.8
-2917.015.5
-2817.716.3
-2718.517.0
-2619.317.7
-2520.118.5
-2420.919.3
-2321.720.1
-2222.620.9
-2123.421.7
-2024.322.6
-1925.223.4
-1826.124.3
-1727.025.2
-1628.026.1
-1528.927.0
-1429.927.9
-1330.928.8
-1231.929.8
-1132.930.8
-1033.931.8
-935.032.8
-836.133.8
-737.134.9
-638.235.9
-539.437.0
-440.538.1
-341.739.2
-242.940.4
-144.141.5
045.342.7
146.543.9
247.845.1
349.046.3
450.347.6
551.748.8
653.050.1
754.351.4
855.752.7
957.154.1
1058.555.4
1160.056.8
1261.458.2
1362.959.7
1464.461.1
1566.062.6
1667.564.1
1769.165.6
1870.767.1
1972.368.7
2073.970.3
2175.671.9
2277.373.5
2379.075.2
2480.776.8
2582.578.5
2684.380.3
2786.182.0
2887.983.8
2989.885.6
3091.787.4
3193.689.2
3295.591.1
3397.593.0
3499.594.9
35101.596.9
36103.598.8
37105.6100.8
38107.7102.9
39109.8104.9
40112.0107.0
41114.1109.1
42116.4111.2
43118.6113.4
44120.9115.6
45123.1117.8
46125.5120.0
47127.8122.3
48130.2124.6
49132.6127.0
50135.0129.3
51137.5131.7
52140.0134.1
53142.5136.6
54145.1139.1
55147.7141.6
56150.3144.1
57153.0146.7
58155.7149.3
59158.4151.9
60161.1154.6
61163.9157.3
62166.7160.1
63169.6162.8
64172.5165.6
65175.4168.5
66178.3171.3
67181.3174.2
68184.4177.2
69187.4180.1
70190.5183.1
71193.6186.2
72196.8189.3
73200.0192.4
74203.2195.5
75206.5198.7
76209.8201.9
77213.1205.2
78216.5208.5
79219.9211.8
80223.4215.2
81226.9218.6
82230.4222.0
83234.0225.5
84237.6229.0
85241.2232.6
86244.9236.2
87248.6239.8
88252.4243.5
89256.2247.2
90260.0251.0
91263.9254.8
92267.9258.6
93271.8262.5
94275.8266.4
95279.9270.4
96284.0274.4
97288.1278.4
98292.3282.5
99296.5286.7
100300.8290.9
101305.1295.1
102309.4299.4
103313.8303.7
104318.3308.0
105322.8312.5
106327.3316.9
107331.9321.4
108336.5326.0
109341.2330.6
110345.9335.2
111350.6339.9
112355.4344.6
113360.3349.4
114365.2354.3
115370.2359.1
116375.2364.1
117380.2369.1
118385.3374.1
119390.5379.2
120395.7384.3
121400.9389.5
122406.2394.8
123411.6400.1
124417.0405.4
125422.4410.8
126427.9416.3
127433.5421.8
128439.1427.4
129444.8433.0
130450.5438.7
131456.3444.5
132462.1450.3
133468.0456.1
134473.9462.0
135479.9468.0
136485.9474.1
137492.1480.2
138498.2486.3
139504.4492.6
140510.7498.8
141517.1505.2
142523.5511.6
143529.9518.1
144536.4524.6
145543.0531.3
146549.6538.0
147556.3544.7
148563.1551.5
149569.9558.4
150576.8565.4

Values in italics with ″ Hg are inches of mercury vacuum (below atmospheric pressure).

About R-454B

TypeBlend: R-32 68.9% / R-1234yf 31.1% (by mass)
Glide at 40°F2.3°F
ASHRAE 34 safety classA2L
GWP (IPCC AR4)466
Used inNew residential and light-commercial air conditioners and heat pumps
Also sold asOpteon XL41, Solstice 454B, Puron Advance

One of the two main R-410A replacements in new US equipment since 2025.

Related charts: R-410A PT chart.

How to read the R-454B PT chart

  1. Read the suction (low-side) pressure and find it in the vapor (dew) column. The temperature in that row is the evaporator saturation temperature. Superheat = suction line temperature − that value.
  2. Read the liquid line (high-side) pressure and find it in the liquid (bubble) column. The temperature in that row is the condenser saturation temperature. Subcooling = that value − liquid line temperature.
  3. Or use the quick lookup above, which gives both values for any pressure.

Need the math done for you? Use the superheat and subcooling calculator for R-454B.

FAQ

What is the pressure of R-454B at 40°F?

112.0 psig liquid / 107.0 psig vapor. 40°F is a typical evaporator saturation temperature for comfort cooling.

What is the pressure of R-454B at 100°F?

300.8 psig liquid / 290.9 psig vapor.

Why does the R-454B chart have two pressure columns?

R-454B is a blend, so it boils and condenses over a range of temperatures (glide). Use the vapor (dew) column to find evaporator saturation for superheat, and the liquid (bubble) column to find condenser saturation for subcooling. At 40°F the glide is about 2.3°F.

Where do these R-454B values come from?

They come from the Chemours published table (NIST REFPROP 10) and are checked against the published Arkema chart. See the data source section below and the methodology page.

Data source and checks

Values from Chemours, Thermodynamic Properties of Opteon XL41 (R-454B), Engineering Units (NIST REFPROP 10). Whole-degree rows between published points are interpolated. Gauge pressure is relative to 14.696 psia (sea level).

Compared with published charts, checked November 24, 2026
Published chartPointsMax difference
Arkema — Forane Refrigerants Pressure Temperature Chart (05-2025)100.05 psi (0.2%)

R-454B values are for pure refrigerant at saturation. How the data is produced and checked.

Reference only — follow the equipment manufacturer's charging instructions.