Refrigerant PT Charts
Pick a refrigerant to open its full pressure–temperature chart with a quick lookup. Blends show separate liquid (bubble) and vapor (dew) pressures.
| Refrigerant | At 40°F, psig | Type |
|---|---|---|
| R-410A PT chart | 118.8 / 118.4 | Blend (liquid / vapor) |
| R-22 PT chart | 68.6 | Single component |
| R-134a PT chart | 35.0 | Single component |
| R-404A PT chart | 86.9 / 85.4 | Blend (liquid / vapor) |
| R-454B PT chart | 112.0 / 107.0 | Blend (liquid / vapor) |
| R-290 PT chart | 63.9 | Single component |
| R-32 PT chart | 121.0 | Single component |
| R-407C PT chart | 80.2 / 63.2 | Blend (liquid / vapor) |
| R-448A PT chart | 89.0 / 72.1 | Blend (liquid / vapor) |
| R-1234yf PT chart | 38.4 | Single component |
What a PT chart tells you
A pressure–temperature (PT) chart lists the saturation pressure of a refrigerant at each temperature — the point where liquid and vapor exist together, as they do inside an evaporator or condenser. Convert a gauge reading to a saturation temperature, then compare it with a line temperature to get superheat or subcooling.
Blends such as R-407C and R-448A change temperature as they boil (temperature glide), so one pressure has two saturation temperatures. Use the vapor (dew) value for superheat and the liquid (bubble) value for subcooling.