R-32 PT Chart
Pressure–temperature chart for R-32, -40 to 150°F in 1° steps. Switch to °C, kPa or bar, or look up a single value.
Quick lookup
Enter a value to get the pressure for R-32.
| Temp °F | Pressure psig |
|---|---|
| -40 | 11.0 |
| -39 | 11.7 |
| -38 | 12.4 |
| -37 | 13.0 |
| -36 | 13.7 |
| -35 | 14.4 |
| -34 | 15.2 |
| -33 | 15.9 |
| -32 | 16.6 |
| -31 | 17.4 |
| -30 | 18.2 |
| -29 | 19.0 |
| -28 | 19.8 |
| -27 | 20.6 |
| -26 | 21.5 |
| -25 | 22.3 |
| -24 | 23.2 |
| -23 | 24.1 |
| -22 | 25.0 |
| -21 | 25.9 |
| -20 | 26.8 |
| -19 | 27.8 |
| -18 | 28.7 |
| -17 | 29.7 |
| -16 | 30.7 |
| -15 | 31.7 |
| -14 | 32.8 |
| -13 | 33.8 |
| -12 | 34.9 |
| -11 | 36.0 |
| -10 | 37.1 |
| -9 | 38.2 |
| -8 | 39.4 |
| -7 | 40.5 |
| -6 | 41.7 |
| -5 | 42.9 |
| -4 | 44.2 |
| -3 | 45.4 |
| -2 | 46.7 |
| -1 | 47.9 |
| 0 | 49.3 |
| 1 | 50.6 |
| 2 | 51.9 |
| 3 | 53.3 |
| 4 | 54.7 |
| 5 | 56.1 |
| 6 | 57.5 |
| 7 | 59.0 |
| 8 | 60.5 |
| 9 | 62.0 |
| 10 | 63.5 |
| 11 | 65.0 |
| 12 | 66.6 |
| 13 | 68.2 |
| 14 | 69.8 |
| 15 | 71.4 |
| 16 | 73.1 |
| 17 | 74.8 |
| 18 | 76.5 |
| 19 | 78.3 |
| 20 | 80.0 |
| 21 | 81.8 |
| 22 | 83.6 |
| 23 | 85.5 |
| 24 | 87.3 |
| 25 | 89.2 |
| 26 | 91.1 |
| 27 | 93.1 |
| 28 | 95.1 |
| 29 | 97.1 |
| 30 | 99.1 |
| 31 | 101.2 |
| 32 | 103.2 |
| 33 | 105.3 |
| 34 | 107.5 |
| 35 | 109.7 |
| 36 | 111.9 |
| 37 | 114.1 |
| 38 | 116.3 |
| 39 | 118.6 |
| 40 | 121.0 |
| 41 | 123.3 |
| 42 | 125.7 |
| 43 | 128.1 |
| 44 | 130.5 |
| 45 | 133.0 |
| 46 | 135.5 |
| 47 | 138.0 |
| 48 | 140.6 |
| 49 | 143.2 |
| 50 | 145.8 |
| 51 | 148.5 |
| 52 | 151.2 |
| 53 | 153.9 |
| 54 | 156.7 |
| 55 | 159.5 |
| 56 | 162.4 |
| 57 | 165.2 |
| 58 | 168.1 |
| 59 | 171.1 |
| 60 | 174.0 |
| 61 | 177.1 |
| 62 | 180.1 |
| 63 | 183.2 |
| 64 | 186.3 |
| 65 | 189.5 |
| 66 | 192.7 |
| 67 | 195.9 |
| 68 | 199.2 |
| 69 | 202.5 |
| 70 | 205.8 |
| 71 | 209.2 |
| 72 | 212.6 |
| 73 | 216.1 |
| 74 | 219.6 |
| 75 | 223.2 |
| 76 | 226.7 |
| 77 | 230.4 |
| 78 | 234.0 |
| 79 | 237.7 |
| 80 | 241.5 |
| 81 | 245.3 |
| 82 | 249.1 |
| 83 | 253.0 |
| 84 | 256.9 |
| 85 | 260.9 |
| 86 | 264.9 |
| 87 | 268.9 |
| 88 | 273.0 |
| 89 | 277.1 |
| 90 | 281.3 |
| 91 | 285.5 |
| 92 | 289.8 |
| 93 | 294.1 |
| 94 | 298.5 |
| 95 | 302.9 |
| 96 | 307.4 |
| 97 | 311.9 |
| 98 | 316.4 |
| 99 | 321.0 |
| 100 | 325.7 |
| 101 | 330.4 |
| 102 | 335.1 |
| 103 | 339.9 |
| 104 | 344.8 |
| 105 | 349.6 |
| 106 | 354.6 |
| 107 | 359.6 |
| 108 | 364.6 |
| 109 | 369.7 |
| 110 | 374.9 |
| 111 | 380.1 |
| 112 | 385.3 |
| 113 | 390.7 |
| 114 | 396.0 |
| 115 | 401.4 |
| 116 | 406.9 |
| 117 | 412.4 |
| 118 | 418.0 |
| 119 | 423.7 |
| 120 | 429.3 |
| 121 | 435.1 |
| 122 | 440.9 |
| 123 | 446.8 |
| 124 | 452.7 |
| 125 | 458.7 |
| 126 | 464.7 |
| 127 | 470.8 |
| 128 | 477.0 |
| 129 | 483.2 |
| 130 | 489.5 |
| 131 | 495.8 |
| 132 | 502.2 |
| 133 | 508.7 |
| 134 | 515.2 |
| 135 | 521.8 |
| 136 | 528.5 |
| 137 | 535.2 |
| 138 | 542.0 |
| 139 | 548.8 |
| 140 | 555.8 |
| 141 | 562.8 |
| 142 | 569.8 |
| 143 | 576.9 |
| 144 | 584.1 |
| 145 | 591.4 |
| 146 | 598.7 |
| 147 | 606.2 |
| 148 | 613.6 |
| 149 | 621.2 |
| 150 | 628.8 |
Values in italics with ″ Hg are inches of mercury vacuum (below atmospheric pressure).
About R-32
| Type | Single-component refrigerant |
|---|---|
| ASHRAE 34 safety class | A2L |
| GWP (IPCC AR4) | 675 |
| Used in | New residential air conditioners, heat pumps and ductless mini-splits |
| Also sold as | HFC-32 |
One of the two main R-410A replacements in new US equipment since 2025.
Related charts: R-410A PT chart.
How to read the R-32 PT chart
- Read the gauge pressure on the low or high side.
- Find that pressure in the chart, or enter it in the quick lookup. The matching temperature is the saturation temperature.
- Superheat = suction line temperature − evaporator saturation temperature. Subcooling = condenser saturation temperature − liquid line temperature.
Need the math done for you? Use the superheat and subcooling calculator for R-32.
FAQ
What is the pressure of R-32 at 40°F?
121.0 psig. 40°F is a typical evaporator saturation temperature for comfort cooling.
What is the pressure of R-32 at 100°F?
325.7 psig.
Where do these R-32 values come from?
They are calculated with the open-source CoolProp 8.1.0 property library and are checked against the published Arkema chart. See the data source section below and the methodology page.
Data source and checks
Calculated with CoolProp 8.1.0 (reference equation of state). Gauge pressure is relative to 14.696 psia (sea level).
| Published chart | Points | Max difference |
|---|---|---|
| Arkema — Forane Refrigerants Pressure Temperature Chart (05-2025) | 5 | 0.05 psi (<0.1%) |
R-32 values are for pure refrigerant at saturation. How the data is produced and checked.
Reference only — follow the equipment manufacturer's charging instructions.