R-407C PT Chart

Pressure–temperature chart for R-407C with liquid (bubble) and vapor (dew) columns, -40 to 150°F in 1° steps. Switch to °C, kPa or bar, or look up a single value.

Printable PDF

Quick lookup

Enter a value to get the pressure for R-407C.

R-407C pressure–temperature chart in °F and psig
Temp °FLiquid bubble, psigVapor dew, psig
-402.74.6″ Hg
-393.23.9″ Hg
-383.73.2″ Hg
-374.12.4″ Hg
-364.61.6″ Hg
-355.10.9″ Hg
-345.60.1″ Hg
-336.10.4
-326.60.8
-317.21.2
-307.71.6
-298.32.1
-288.82.5
-279.43.0
-2610.03.5
-2510.63.9
-2411.24.4
-2311.84.9
-2212.45.4
-2113.15.9
-2013.76.5
-1914.47.0
-1815.17.6
-1715.88.1
-1616.58.7
-1517.29.3
-1417.99.9
-1318.710.5
-1219.411.1
-1120.211.7
-1020.912.3
-921.713.0
-822.513.7
-723.414.3
-624.215.0
-525.015.7
-425.916.4
-326.817.2
-227.717.9
-128.618.7
029.519.4
130.420.2
231.421.0
332.321.8
433.322.6
534.323.5
635.324.3
736.425.2
837.426.1
938.527.0
1039.527.9
1140.628.8
1241.729.8
1342.930.7
1444.031.7
1545.232.7
1646.333.7
1747.534.7
1848.735.7
1950.036.8
2051.237.9
2152.539.0
2253.840.1
2355.141.2
2456.442.3
2557.743.5
2659.144.7
2760.545.9
2861.947.1
2963.348.3
3064.749.6
3166.250.8
3267.752.1
3369.253.4
3470.754.8
3572.256.1
3673.857.5
3775.458.9
3877.060.3
3978.661.7
4080.263.2
4181.964.6
4283.666.1
4385.367.6
4487.069.2
4588.870.7
4690.672.3
4792.473.9
4894.275.5
4996.077.2
5097.978.8
5199.880.5
52101.782.2
53103.784.0
54105.685.7
55107.687.5
56109.689.3
57111.791.2
58113.793.0
59115.894.9
60117.996.8
61120.198.7
62122.2100.7
63124.4102.7
64126.7104.7
65128.9106.7
66131.2108.8
67133.5110.9
68135.8113.0
69138.1115.1
70140.5117.3
71142.9119.5
72145.4121.7
73147.8124.0
74150.3126.2
75152.8128.5
76155.4130.9
77157.9133.2
78160.5135.6
79163.2138.0
80165.8140.5
81168.5143.0
82171.2145.5
83174.0148.0
84176.8150.6
85179.6153.2
86182.4155.8
87185.3158.5
88188.2161.2
89191.1163.9
90194.1166.7
91197.1169.5
92200.1172.3
93203.2175.2
94206.2178.1
95209.4181.0
96212.5183.9
97215.7186.9
98218.9189.9
99222.2193.0
100225.5196.1
101228.8199.2
102232.1202.4
103235.5205.6
104239.0208.8
105242.4212.1
106245.9215.4
107249.4218.8
108253.0222.1
109256.6225.6
110260.2229.0
111263.9232.5
112267.6236.1
113271.3239.6
114275.1243.2
115278.9246.9
116282.8250.6
117286.7254.3
118290.6258.1
119294.6261.9
120298.6265.8
121302.6269.6
122306.7273.6
123310.8277.6
124315.0281.6
125319.2285.6
126323.4289.8
127327.7293.9
128332.0298.1
129336.3302.3
130340.7306.6
131345.2311.0
132349.7315.3
133354.2319.8
134358.7324.2
135363.3328.7
136368.0333.3
137372.7337.9
138377.4342.6
139382.2347.3
140387.0352.0
141391.8356.9
142396.7361.7
143401.7366.6
144406.7371.6
145411.7376.6
146416.8381.7
147421.9386.8
148427.1392.0
149432.3397.2
150437.5402.5

Values in italics with ″ Hg are inches of mercury vacuum (below atmospheric pressure).

About R-407C

TypeBlend: R-32 23% / R-125 25% / R-134a 52% (by mass)
Glide at 40°F11.1°F
ASHRAE 34 safety classA1
GWP (IPCC AR4)1,774
Used inRetrofits of R-22 air conditioning and chillers
Also sold asSuva 407C, Genetron 407C

Common R-22 retrofit refrigerant; has a large temperature glide.

Related charts: R-22 PT chart.

How to read the R-407C PT chart

  1. Read the suction (low-side) pressure and find it in the vapor (dew) column. The temperature in that row is the evaporator saturation temperature. Superheat = suction line temperature − that value.
  2. Read the liquid line (high-side) pressure and find it in the liquid (bubble) column. The temperature in that row is the condenser saturation temperature. Subcooling = that value − liquid line temperature.
  3. Or use the quick lookup above, which gives both values for any pressure.

Need the math done for you? Use the superheat and subcooling calculator for R-407C.

FAQ

What is the pressure of R-407C at 40°F?

80.2 psig liquid / 63.2 psig vapor. 40°F is a typical evaporator saturation temperature for comfort cooling.

What is the pressure of R-407C at 100°F?

225.5 psig liquid / 196.1 psig vapor.

Why does the R-407C chart have two pressure columns?

R-407C is a blend, so it boils and condenses over a range of temperatures (glide). Use the vapor (dew) column to find evaporator saturation for superheat, and the liquid (bubble) column to find condenser saturation for subcooling. At 40°F the glide is about 11.1°F.

Where do these R-407C values come from?

They are calculated with the open-source CoolProp 8.1.0 property library and are checked against the published Arkema chart. See the data source section below and the methodology page.

Data source and checks

Calculated with CoolProp 8.1.0 (pseudo-pure fluid model). Gauge pressure is relative to 14.696 psia (sea level).

Compared with published charts, checked November 24, 2026
Published chartPointsMax difference
Arkema — Forane Refrigerants Pressure Temperature Chart (05-2025)100.07 psi (<0.1%)

R-407C values are for pure refrigerant at saturation. How the data is produced and checked.

Reference only — follow the equipment manufacturer's charging instructions.